Case: T10FR01632

Parcel: 12317201C


Addresses:

1449 N CHERRY AV

Inspection Status: Continued

Inspection History: INSP - FULL

Date Description Inspector Results Comments
08/05/2010 INSP - FULL Continued When test fired, frier did not shut down
System remote pull station is Ansul Pull not Pyro Chem pull station
Remote pull is too high and is not at the point of exit
System needs to be tied into an alarm system
Electrical does not shut down