Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

FIELD

Type:

COMPLAINT (COMMERCIAL)
Address:

Entered Date:

08/05/2010

Applicant:

PI KAPPA PHI PROPERTIES INC

Description:

Deficiencies - CINTAS

Outstanding Inspections

Case Number: T10FR01632
Case Status: FIELD
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
08/05/2010 INSP - FULL CDevine1 Continued When test fired, frier did not shut down System remote pull station is Ansul Pull not Pyro Chem pull station Remote pull is too high and is not at the point of exit System needs to be tied into an alarm system Electrical does not shut down