Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2010 | INSP - FULL | Correction Required | RED TAG - 17A 4.4.3.1 - ALL SOURCES OF FUEL AND ELECTRICAL POWER TO ALL APPLIANCES SALL BE SHUT DOWN 96 8.3.2 - MAKE UP AIR SUPPLIED INTERNALLY TO THE HOOD SHALL SHUT DOWN ON ACTIVATION System is a pre-UL300 wet agent system. UFEC recommends upgrading to a UL300 compliant system |