Case: T10FR01336
Case Details
Entered Date:
07/14/2010
Applicant:
EEGEES INC
Description:
DISCREPANCIES - UNITED FIRE
Outstanding Inspections
Case Number: T10FR01336
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2010 | INSP - FULL | CDEVINE1 | Correction Required | RED TAG - 17A 4.4.3.1 - ALL SOURCES OF FUEL AND ELECTRICAL POWER TO ALL APPLIANCES SALL BE SHUT DOWN 96 8.3.2 - MAKE UP AIR SUPPLIED INTERNALLY TO THE HOOD SHALL SHUT DOWN ON ACTIVATION System is a pre-UL300 wet agent system. UFEC recommends upgrading to a UL300 compliant system |
| 07/20/2010 | VIOL - FIRE PROTECTION SYSTEMS | MPursley | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Fire protection systems and equipment shall be inspected, tested and maintained. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR01336
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2010 | COMPLIANCE | MPursley | Approved | System is as designed with no changes. No repairs need to be made. |