Case Details

Status:

COMPLETE

Type:

COMPLAINT (COMMERCIAL)

Entered Date:

07/14/2010

Applicant:

EEGEES INC

Description:

DISCREPANCIES - UNITED FIRE

Outstanding Inspections

Case Number: T10FR01336
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
07/14/2010 INSP - FULL CDEVINE1 Correction Required RED TAG - 17A 4.4.3.1 - ALL SOURCES OF FUEL AND ELECTRICAL POWER TO ALL APPLIANCES SALL BE SHUT DOWN 96 8.3.2 - MAKE UP AIR SUPPLIED INTERNALLY TO THE HOOD SHALL SHUT DOWN ON ACTIVATION System is a pre-UL300 wet agent system. UFEC recommends upgrading to a UL300 compliant system
07/20/2010 VIOL - FIRE PROTECTION SYSTEMS MPursley Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Fire protection systems and equipment shall be inspected, tested and maintained.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR01336
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/02/2010 COMPLIANCE MPursley Approved System is as designed with no changes. No repairs need to be made.