Inspection Status: Violation
Inspection History: VIOL - PRECAUTION AGAINST FIRE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/25/2010 |
VIOL - PRECAUTION AGAINST FIRE |
|
Violation |
308.3.1.1 Liquefied-petroleum-gas-fueled cooking devices. LP-gas burners having an LP-gas container with a water capacity greater than 2.5 pounds [nominal 1 pound (0.454 kg) LP-gas capacity] shall not be located on combustible balconies or within 10 feet (3048 mm) of combustible construction. |
| 06/25/2010 |
VIOL - PRECAUTION AGAINST FIRE |
|
Violation |
309.4 Fire extinguishers. Battery-charging areas shall be provided with a fire extinguisher complying with Section 906 having a minimum 4-A:20-B:C rating within 20 feet (6096 mm) of the battery charger. |
| 06/25/2010 |
VIOL - PRECAUTION AGAINST FIRE |
|
Violation |
315.2.1 - Ceiling clearance. Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings. |