Case: T10FR01262

Parcel: 13709006A


Addresses:

5330 S 12TH AV


Inspection Status: Violation

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T10FR01262

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
06/25/2010 VIOL - FIRE PROTECTION SYSTEMS Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
_____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag
shall be affixed to the extinguisher with records of these activities.
06/25/2010 VIOL - FIRE PROTECTION SYSTEMS Violation 904.1 General. Automatic fire-extinguishing systems, other than automatic sprinkler systems, shall be designed, installed, inspected, tested and maintained in accordance with the provisions of this section and the applicable referenced standards.
__ Provide coverage for all cooking appliances under hoods.
06/25/2010 VIOL - FIRE PROTECTION SYSTEMS Violation 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.
06/25/2010 VIOL - FIRE PROTECTION SYSTEMS Violation 904.5.1 System test. Systems shall be inspected and tested for proper operation at 6-month intervals. Tests shall include a check of the detection system, alarms and releasing devices, including manual stations and other associated equipment.