Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - FULL
Case Number - T10FR00929
Inspection Description - INSP - FULL
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/07/2010 | INSP - FULL | Correction Required | Electric does not shut down upon system activation/All fryers are electric and gas operated Breaker panel has shunt trip breakers for fryer shut down but failed to shut down upon activation System is also due for a hydro test and cartridge replacement in 2010 |