Description:

Deficiencies - United Fire

Outstanding Inspections

Case Number: T10FR00929
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
05/07/2010 INSP - FULL CDevine1 Correction Required Electric does not shut down upon system activation/All fryers are electric and gas operated Breaker panel has shunt trip breakers for fryer shut down but failed to shut down upon activation System is also due for a hydro test and cartridge replacement in 2010

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00929
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/18/2010 INSP - REINSPECTION JLOYA Approved Electric shut down fixed, manager provided invoice from electrical contractor. Hydro test still pending.