Case: T10FR00734

Parcel: 11506207B


Addresses:

1801 N STONE AV


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T10FR00734

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
04/13/2010 VIOL - MEANS OF EGRESS Correction Required 1008.1.8.4 Bolt locks.
Manually operated flush bolts or surface bolts are not permitted.

_____ Remove the slide bolt from the DJ booth door, the west kitchen door, and the Electrical room door, as bolt lock of any kind are not permitted.

1008.1.8 Door operations.
Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

_____ Remove the double-key lock and replace with an approved locking device such as, thumb turn lock or panic hardware (West Kicthen door, Janitor door)

1008.1.8.5 Unlatching.
The unlatching of any door or leaf shall not require more than one operation.

1008.1.8.3 Locks and latches.
Locks and latches shall be permitted to prevent operation of doors where any of the following exists…
-- 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress
side provided:
-- 2.1. The locking device is readily distinguishable as locked,
-- 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background,
-- 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause.

_____ Place the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" visibly above your main
egress door.

1027.3 Exit sign illumination.
Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose.

_____ Fix, repair, and/or replace all non-working exit signs in order to meet code standards (north exit)