Case: T10FR00378

Parcel: 12111001B


Addresses:

5055 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
04/22/2010 VIOL - FIRE PROTECTION SYSTEMS Approved ALL VIOLATIONS CORRECTED.
02/19/2010 VIOL - FIRE PROTECTION SYSTEMS Correction Required 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or
removed.

1____SPRINKLER CONNECTIONS NEED TO BE FIXED WONT TURN.
2____NEED TO SHOW REPORT THAT SPRINKLERS HAS BEEN INSPECTED, WITHIN THE YEAR.
02/19/2010 VIOL - FIRE PROTECTION SYSTEMS Correction Required 912.2.2 Existing buildings. On existing buildings, wherever
the fire department connection is not visible to
approaching fire apparatus, the fire department connection
shall be indicated by an approved sign mounted on the street
front or on the side of the building. Such sign shall have the
letters “FDC” at least 6 inches (152 mm) high and words in
letters at least 2 inches (51 mm) high or an arrow to indicate
the location. All such signs shall be subject to the approval
of the fire code official.

1___NEED SIGN ON FRONT OF BUILDING SHOWING LOCATION OF FDC.