Case: T10FR00350

Parcel: 13316027E

Inspection Status: Correction Required

Inspection History: VIOL - HAZARDOUS MATERIALS,GEN

Date Description Inspector Results Comments
02/11/2010 VIOL - HAZARDOUS MATERIALS,GEN Correction Required 2703.5 Hazard identification signs.
Unless otherwise exempted by the fire code official, visible hazard identification signs as specified in NFPA 704 for the specific material contained shall be placed on stationary containers and above-ground tanks and at entrances to locations where hazardous materials are stored, dispensed, used or handled in quantities requiring a permit and at specific entrances and locations designated by the fire code official.

_____Place appropriate marking

2703.1.1 Maximum allowable quantity per control area.
The maximum allowable quantity per control area shall be
as specified in Tables 2703.1.1(1) through 2703.1.1(4).

_____Limit O2 to Maximum Allowable Quantities or build appropriately constructed containment area.

2703.7.1 Smoking.
Smoking shall be prohibited and "NoSmoking" signs provided

_____Place No Smoking signs in containment area