Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/05/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WATER LINE ALONE NOT ENOUGH AS REQUIRED PER 250 NEC-INSTALL GROUND RODS AS REQUIRED PER 250.50 OR LOCATE EXISTING UFER 2) NUTS NOT COMPLETELY SEATED ON ADDED LUGS IN SERVICE DISCONNECT 3) 60 AMP DISCONNECT IS NOT RATED FOR OUTDOOR USE-IF YOUR GOING TO KEEP USING IT REPLACE WITH NEMA 3R AS REQUIRED BY CODE 4) SEE NOTE #8 INSPECTION ON 12/27/10 A REINSPECTION FEE WILL BE ASSESED NEXT INSPECTION IF WORK NOT DONE PROPERLY |
|
| 01/03/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO COMPLIANCE NOTE: #1 LAST INSPECTION 2) GROUNDING ELECTRODE CONDUCTOR TO SERVICES MISSING. THIS IS A LIFE SAFETY ISSUE AND NEEDS TO BE ADDRESSED ASAP, OTHER TENANTS ALSO 3) OK INSIDE INSPECTION |
|
| 12/27/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CANNOT DBL LUG CONDUCTORS IN SERVICE DISCONNECT 2) UNSAFE WIRING AT 2727 IN BACK AND IS ATTACHED TO 2525 METAL SHADE STRUCTURE 3) EXPOSED WIRING AT OUTSIDE FRONT WHERE SIGN USED TO BE 4) SUPPORT CONDUITS, PLUG HOLES IN RECEPT BOXES INSIDE BLDG, ALSO RECEPTS NOT INSTALLED IN BOXES (HANGING OUT ?) 5) EXPOSED WIRING INSIDE BACK AREA BY PANEL, FLOURESCENT FIXTURE MISSING COVER 6) CUT OFF EXTENSION CORDS CANNOT BE USED AS WIRING METHOD OUTSIDE BACK OF BLDG, ALSO RECEPTS MISSING COVERS 7) HAVE ELECTRICIAN CHECK OUT ROOF AND REPAIR ELECTRIC, HAVE LADDER ON SITE NEXT INSPECTION 8) USE LICENSED OR QUALIFIED ELECTRICIAN TO DO WORK |