Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/05/2011 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) RECALL WHEN SWING OVER IS COMPLETE |
|
| 01/04/2011 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO COMPLY WITH ALL PREVIOUS INSPECTION ITEMS |
|
| 12/14/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED PROPER WORKING CLEARANCE IN FRONT OF PANEL MIN 36" DEEP 2) GROUND RODS TO BE MINIMUM 6' APART 3) NEED MINIMUM 24" ON NEUTRAL OUT OF WEATHERHEAD 4) BOND WATER PIPING 5) LUGS ON GROUND ROD ONLY LISTED FOR 1 WIRE TERMINATION 6) VERIFY WITH TEP LOCATION OF NEW SERVICE IS ACCEPTABLE |