Permit: T10EL02646

Parcel: 12008257A


Addresses:

4709 S 7TH AV #02

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/24/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REMOVE ZIP CORD WIRING FROM FRONT PORCH LIGHT. ALSO FIXTURE BROKEN
2) EXPOSED/OPEN CONDUCTORS IN FRONT WALL AT SWITCH
3) KITCHEN RECEPT TO BE GFI PROTECTED-FILL UNUSED OPENING IN BOX
4) REATTACH BOX IN CLOSET AND PROTECT BULB
5) GROUNDED RECEPTS ON NON GROUNED CIRCUITS
6) SUPPORT CONDUIT BEDROOMS
7) REPLACE COVERS AT MAIN BREAKER
8) MISSING DEAD FRONT COVER PANEL
9) JUNCTION BOX/OLD PANEL ABOVE PANEL NOT LEGAL PER CODE
10) BOND JUMPER CANNOT BE WHITE 200.6
11) WROUGHT IRON WINDOWS NEED QUICK RELEASE
12) SMOKE DETECTORS 3' FROM DUCTS AND 7-9" DOWN