Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/24/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/09/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GFI PROTECT BATHROOM OUTLET ON FIXTURE 2) SMOKE DETECTORS NEEDED IN BEDROOMS 3) SMOKE DETECTOR IN HALLWAY NEEDS TO BE WORKING 4) ILLEGAL ADDITION AT BACK ENCLOSED EGRESS FOR MASTER BEDROOM 5) NEED ACCESS TO UTILITY ROOM OFF BACK 6) BLANK OFF OPEN SPACES AT PANEL 7) GFI PROTECT ALL COUNTER RECEPTS IN KITCHEN 8) LABEL ALL CIRCUITS AT PANEL 9) BLANK UNUSED KNOCKOUTS AT PANEL 10) GFI PROTECT EXTERIOR OUTLETS 11) DISHWASHER NEEDS TO BE ON DEDICATED CIRCUIT NOT INTO COUNTER RECEPTS 12) REMOVE UNUSED CONDCUCTOR IN ADDITION AT REAR |