Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/02/2010 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 08/27/2010 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* EAST BLDG: 1) FILL UNUSED OPENINGS IN BOXES 2) RE-SUPPORT CONDUIT ON EXTERIOR AND INTERIOR 3) BOXES OVER FILLED 4) PROTECT NM CABLES 5) MISSING COVER PLATES 6) SEPERATED CONDUITS 7) GROUND PANEL DISCONNECT PER 250.8 + 12 AND 110.14 WEST BLDG: 1) DBL LUGGING AT MAIN DISCONNECT OUTSIDE 2) FILL UNUSED OPENINGS BOXES AND PANEL |