Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/27/2010 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 09/15/2010 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) BOTTOM 3 RACEWAYS ARE AT CODE DEPTHS PER 300.5 2) TOP 2 ARE NOT, CAP OFF TOP RUNS 3) COMBINED RUNS WILL BE OK FOR DERATING PER 310.15 FOR CONDUCTOR |