Permit: T10EL00486

Parcel: 127021340


Addresses:

5212 E 3RD ST

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/08/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) KITCHEN COUNTER RECEPTS TO BE GFI PROTECTED
2) OUTDOOR RECEPTS TO BE GFI PROTECTED
3) BATHROOM RECEPTS TO BE GFI PROTECTED
4) HAVE EXPOSED WIRING AT DBL OVEN LOCATION
5) HAVE GROUNDING TYPE RECEPTS ON UNGROUNDED 2 WIRE SYSTEM
6) MISSING WALL PLATES
7) HAVE BROKEN RECEPTS
8) WIRE HANGING OUT OF CEILING MSTR BEDROOM
9) NON CODE COMPLIANT TAPS AT SERVICE
10) EQUIPMENT AND WIRING TO SPA/HOT TUB EXPOSED TO WEATHER
11) BLANK OPEN BREAKER POSITIONS IN PANEL
12) CLOSET LIGHTS TO BE 100 PERCENT ENCLOSED
13) HAVE QUALIFIED ELECTRICAL CONTRACTOR MAKE REPAIRS AND GO THRU ENTIRE HOME & CHECK WIRING SYSTEM