Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) KITCHEN COUNTER RECEPTS NEED TO BE GFI PROTECTED 2) SMOKE DETECTORS IN NORTH BEDROOMS TO CLOSE TO A/C REGISTERS, SHOULD BE AT LEAST 3' AWAY 3) SERVICE EQUIPMENT OUT DATED AND NOT TO CODE-EXPOSED CABLES, DBL LUGGING ON LOAD AND LINE SIDE OF MAIN SERVICE DISCONNECT. EQUIPMENT NOT RATED FOR OUTDOOR USE 4) RECEPTS ON BACK WALL AND STORAGE NOT TO CODE 5) SERVICE NOT GROUNDED 6) UPGRADE SERVICE AND OTHER CORRECTIONS AND RECALL INSPECTION, OBTAIN SERVICE UPGRADE PERMIT OR ADD TO THIS ONE 7) USE QUALIFIED OR LICENSED ELECTRICIAN |