Permit: T10EL00141

Parcel: 138160170

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/28/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/25/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) KITCHEN RECEPTS TO BE GFCI PROTECTED
2) BATHROOM RECEPTS TO BE GFCI PROTECTED
3) SMOKE DETECTORS NEEDED IN BEDROOMS-INSTALL AS PER INSTRUCTIONS
4) MAIN BREAKER AMPACITY TO MATCH RECEPT AND LIFE LINE
5) SECURE ELECTRIC PANEL TO WALL
6) EXPOSED NM CABLE
7) PROPERLY SECURE LIFE LINE TO INTERIOR PANEL
8) PLEASE OBTAIN SERVICES OF QUALIFIED ELECTRICIAN
9) DO NOT OCCUPY WITHOUT ELECTRICITY ON