Inspection Status: Approved
Inspection History: INSP - FOLLOW UP CODE ENFORCE
| Date |
Description |
Inspector |
Results |
Comments |
| 12/29/2010 |
INSP - FOLLOW UP CODE ENFORCE |
|
Approved |
F/U INSP FOUND ALL KITCHEN AND BATH PLUMBING FIXTURES DRAINING PORPERLY. COMPLIANCE CLOSE CASE. PROPERTY MANAGER LANNY COLTON CALLED AND MENTIONED SEWER LINE BEHIND UNIT #8 WILL BE REPLACED. |
| 12/14/2010 |
INSP - FOLLOW UP CODE ENFORCE |
|
Notice of violation |
|
| 12/10/2010 |
INSP - FOLLOW UP CODE ENFORCE |
|
Follow-up inspection |
|
| 12/10/2010 |
INSP - FOLLOW UP CODE ENFORCE |
|
Approved |
Case has been reopened due to owner calling about the vanity sink draining very slowly and that a second blockage in the sewer line had occurred just after Thanksgiving although tenants were not at home ( sewage did back up into the tub). * did visit the property and found bath vanity sink draining very, very slowly. Filled 1/2 the sink and it took over 2 minutes to drain.Nov will be issued for the drain, and if a third blockage in the sewer line occurs, HCD will ask that a third party scopes the sewer line to determine the cause of blockage, so that HCD inspector can determine how to abate. |