Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2011 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
| 12/16/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 12/15/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 12/06/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 11/29/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 11/22/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK RP1B AND RP1A-CONTRACTOR TO MAINTAIN LOCK OUT/TAG OUT |
|
| 11/18/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) WORKING CLEARANCE AH3 2) NEED LABELING 3) OK 1ST FLOOR CEILING EXCEPT AS NOTED 4) OK CHILLER 5) OK SWITCH GEAR 4 UNDER LO/TO 6) RECEIVED LETTER OF TORQUE |
|
| 10/28/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK NORTH STAIRWELL LID 206A 2) OK TO BARRIER PAPER HALL 106A |
|
| 10/20/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) CAP UNUSED CONDUIT OPENINGS 2) WILL NEED LETTER OF TORQUE 3) SPLIT BOLT FOR ONLY A RUN AND A TAP 4) NO MORE THAN 360 DEGREE IN CONDUIT RUN 5) OK TO ENERGIZE ELECTRICAL EQUIPMENT PER LOCK OUT/TAG OUT 6) RECEIVED CHECK #2029 FOR $165.00 |
|
| 10/14/2011 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) USE APPROVED HARDWARE 2) POWER ENERGIZED WITHOUT CLEARANCE |
|
| 10/13/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) SECURE TRANSFORMER TO PAD 2) WHERE IS GEC CONNECTION TO GROUNDED TERMINAL ? 3) PROTECT CONDUCTOR 300.4 4) FILL UNUSED OPENINGS 5) CLEANOUT FOREIGN MATERIAL AND DIRT FROM EQUIPMENT |
|
| 10/12/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 09/28/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 09/14/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK SES PAD AT NEW BLDG |
|
| 07/26/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 07/25/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 07/21/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 07/20/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* |