Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/16/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 12/15/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FINISH GROUNDING WATER HEATER 2) LABEL DISCONNECTS AND EQUIPMENT 3) BOXES 314.20 4) CHECK EM SYSTEMS 5) OK 1ST FLOOR CLASSROOM |
|
| 11/18/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 10/12/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 2ND FLOOR WALLS, SOUTH STAIRWELL LID ON 2ND FLOOR AND BATHROOM LIDS |
|
| 09/28/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS ROOMS 101-111 |
|
| 07/26/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK IN BLOCK WALLS |
|
| 07/25/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 2 STORY EXISTING BLDG-FIRE ALARM RUNS AND BOXES |
|
| 07/21/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NORTH CLASSROOMS: 1) IDENTIFY FIRE ALARM BOXDS 760.9 2) EXISTING CONDUIT RUN MORE THAN 360 DEGREE BLDG 101 3) FILL UNUSED OPENINGS IN BOXES 4) OK CENTRAL AND SOUTH CLASSROOMS (EAST & WEST), ADMIN/MPR FIRE ALARM CONDUITS AND BOXES |
|
| 07/20/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NO MORE THAN 360 DEGREE IN CONDUIT RUNS 2) SUPPORT CONDUITS 3' OF BOXES 3) JUNCTION BOXES TO BE ACCESSIBLE |
|
| 07/19/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SUPOORT FLEX OFF GRID 2) VERIFY BOX FILL |
|
| 07/18/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* PLEASE OPEN CEILING TO INSPECT |