Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/20/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/05/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDUIT IS SUPPORTING BLOCKS-USE APPROVED METHODS FOR SUPPORTING CONDUIT 2) NO MORE THAN 360 DEGREE IN CONDUIT RUNS 3) FINISH #6 PREVIOUS INSPECTION 4) PROVIDE OSHA APPROVED LADDER INSTALLED AND TIED OFF 5) A REFEE MAY BE ASSESED IF ALL ITEMS NOT COMPLETED FOR NEXT INSPECTION |
|
| 12/22/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SECURE BLOCK TO ROOF WITH TAR OR SUTIABLE PRODUCTS 2) TIGHTEN LOOSE LUG CONNECTIONS 3) ONLY ONE CONDUCTOR PER LUG CONNECTION 4) TIGHTEN LOOSE FITTINGS 5) PROVIDE PHSYICAL PROTECTION FOR PV CONDUITS 6) INSTALL WEEB LUGS PER MANUFACTURES INSTRUCTIONS 7) LABEL SERVICE PANEL PER 690.17 |