Permit: T10CM03257

Parcel: 117022420


Addresses:

941 N 4TH AV


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T10CM03257

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
06/05/2012 ELECTRIC - UNDERGROUND Approved
06/04/2012 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) USE APPROVED CONNECTIONS TO BOND WIRE
05/30/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK #8 BONDS FLAT DECK FOR WATER SPLASH PAD
2) COOL DECK BOND TO BE 18"-24" FROM EDGE-BOND ALL METAL WITHIN 5' OF EDGE
04/05/2012 ELECTRIC - UNDERGROUND Partial Approval RUN FROM NEW SERVICE TO PUMP HOUSE AND TO RESTROOM BLD OK
03/23/2012 ELECTRIC - UNDERGROUND Partial Approval PUMP HOUSE OK.
WADING POOL BONDING OK

REQUIRED, BUT NOT SHOWN ON PLANS IS AN EQUIPOTENTIAL BONDING GRID PER NEC 680.26(C) AT SPLASH PAD.
02/08/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
02/08/2012 ELECTRIC - UNDERGROUND Partial Approval