Permit: T10CM03245

Parcel: 10606031D


Addresses:

1020 W PRINCE RD

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/27/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
01/26/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP
2) I.W. WASTE OVER FIVE FEET TO BE DIRECTLY TRAPPED
3) PROVIDE METHOD OF STERILIZATION
4) PROVIDE LISTING FOR STUDER VENT TO BE INSTALLED HORIZONTALLY
12/16/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) REVIEWED INSPECTION PROCESS WITH OWNER
2) HAVE LICENSED PLUMBER REVIEW PLAN, OPEN UP AREAS COVERED WITHOUT INSPECTION
3) INDIRECT WASTES MAY NOT BE COMBINED
4) SINKS AND 2 COMP OF 3 COMP SINK TO DRAIN DIRECTLY INTO S.S.
5) BACK FLOW PROTECTION, BACK FLOW CERT, CLEAN BACTERIA REPORT AND METHOD OF STERILIZATION
6) PROVIDE ISOMETRIC FOR WASTE PIPING AT NEW BAR AREA