Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/10/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* 1) OK CEILING AND EXPOSED WIRING |
|
| 02/09/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. FILL UNUSED OPENINGS IN BOXES 2. FAN BOXES ALSO OVER FILLED 3. VERIFY CORD CONNECTION OF DISH WASHER 4. SUPPORT M/C CABLES FOR EXIT SIGNS |
|
| 02/07/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLANS STILL NOT REFLECTIVE OF WORK PERFORMED - NEW + OLD 2. BOXES OVER FILLED 3. RACK WAYS SEPERATED AT COUPLINGS 4. BOXES NEED CONNECTOR FOR CABLES 312.5 (E) 5. BOXES TO BE RATED FOR CEILING FAN |
|
| 01/31/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) PLANS NOT REFLECTIVE OF NEW OR EXISTING WORK INSTALLED OR TO BE INSTALLED |