Permit: T10CM03189

Parcel: 110052090


Addresses:

4421 E PRESIDIO PL

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
02/04/2011 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
01/11/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) TYPE B VENT REQUIRES 1" MINIMUM CLEARANCE FROM COMBUSTIBLES
2) ACCESS TO ATTIC TUBING
12/02/2010 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) GAS WATER HEATER REQUIRES 6" CLEARANCE IN FRONT OF BURNER
2) SEDIMENT TRAP REQ ON GAS SUPPLY
3) TYPE B VENT REQUIRED. SINGLE WALL TOUCHING WOOD IS A FIRE HAZARD. MIN TERMINATION IS 1' ABOVE ROOF
4) PROTECT TUBING PASSING THRU BRICK, AND RUBBING ON BACK
5) BEND OVER NAILS POKING THRU
6) SUPPORT ALL DOMESTIC PIPING
7) PROVIDE ACCESS TO TUBING IN ATTIC SPACE
8) SUPPORT AND PROTECT AS REQ.