Date Description Inspector Results Comments
05/31/2011 ELECTRIC - PROGRESS Approved
05/11/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) LOCK OUT TAG OUT TO FINAL DISC. AT 480V
2) LETTER OF TORQUE
3) SUPPORT CONDUIT AT ARRAY PER CODE
4) BUSHINGS AT CONDUIT ENTRYS
5) NOT READY AT EXISTING SERVICE, COPY OF HI POT 5KV FEEDERS