Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T10CM03018
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/31/2011 | ELECTRIC - PROGRESS | Approved | ||
05/11/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) LOCK OUT TAG OUT TO FINAL DISC. AT 480V 2) LETTER OF TORQUE 3) SUPPORT CONDUIT AT ARRAY PER CODE 4) BUSHINGS AT CONDUIT ENTRYS 5) NOT READY AT EXISTING SERVICE, COPY OF HI POT 5KV FEEDERS |