Permit: T10CM02874

Parcel: 116193760

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
02/28/2012 FIRE - ALARM FINAL Approved
01/23/2012 FIRE - ALARM FINAL Partial Approval Still need to do fire pump test
Tested all tamper in fire pump room and stairwells
Need to wire tamper switch to panel for stairwell #1 standpipe butterfly valve
Tested all water flows, in stairwell #2 flow switch failed on 2nd floor went off at 4 sec. min 30 max 2 mins
Need to wire tamper and flow switches in annex garage area