Permit: T10CM02562

Parcel: 12416017A


Addresses:

602 E 22ND ST


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T10CM02562

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
11/23/2010 MECHANICAL - ABOVE CEILING Approved
11/18/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. REMOVE BRACKETS DISABLING FLEX CONECTOR.
2. PROVIDE ROMEX CLAMP AT CONTROL WIRING ENTERING FC-CABINET.
3. FC-4 T0STAT WIRING DISABLED?
4. PAINT BLACK INSIDE RETURN CANS THAT ARE VISIBLE.
5. PROVIDE ARE BALANCE REPORT.
10/26/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) DUCT ABOVE I.T. ROOM OK TO COVER
10/21/2010 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*