Permit: T10CM02502

Parcel: 121060070


Addresses:

5609 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
03/24/2011 FIRE - FINAL Approved Approved 3/24/11
03/22/2011 FIRE - FINAL Cancelled IVRS - RI canceled
03/17/2011 FIRE - FINAL Denied Not approved 3/17/11
1.) need self-closing hardware on all doors on deminishing wall.
2.) Need to add 4 illuminated directional exit signs as noted on page E-3 on approved floor plans.
3.) Must remove all door stops from all fire rated doors.