Permit: T10CM02502

Parcel: 121060070


Addresses:

5609 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T10CM02502

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
01/06/2011 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1) PAINT ALL EXPOSED PVC WITH LATEX PAINT
2) 2 CONDENSATE TRAPS INSTALLED BACKWARDS
3) I.D. UNIT DATA PLATES WITH PROPER HEAT STRIP AND PROVIDE EQUAL OVER CURRENT PROTECTION
4) PROVIDE AIR BALANCE FOR OUTSIDE AIR
5) REPAIR ONE KINKED FLEX DUC
6) WILL CHECK AT FINAL
12/30/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE MINIMUM R-8 FLEX DUCT
2) PROVIDE SEISMIC RETRAINTS ON ALL T-BAR REGISTERS
3) PROVIDE MINIMUM 2" BEADED COLLARS AT ALL FLEX DUCT CONNECTIONS
4) COMPLETE DUCT STEALING AND DUCT WRAP
5) VERIFY 2" LINER IN LINED DUCT DROPS