Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T10CM02502
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2011 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1) PAINT ALL EXPOSED PVC WITH LATEX PAINT 2) 2 CONDENSATE TRAPS INSTALLED BACKWARDS 3) I.D. UNIT DATA PLATES WITH PROPER HEAT STRIP AND PROVIDE EQUAL OVER CURRENT PROTECTION 4) PROVIDE AIR BALANCE FOR OUTSIDE AIR 5) REPAIR ONE KINKED FLEX DUC 6) WILL CHECK AT FINAL |
|
| 12/30/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE MINIMUM R-8 FLEX DUCT 2) PROVIDE SEISMIC RETRAINTS ON ALL T-BAR REGISTERS 3) PROVIDE MINIMUM 2" BEADED COLLARS AT ALL FLEX DUCT CONNECTIONS 4) COMPLETE DUCT STEALING AND DUCT WRAP 5) VERIFY 2" LINER IN LINED DUCT DROPS |