Permit: T10CM02281

Parcel: 12801005H

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T10CM02281

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
02/02/2011 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
APPROVED- FOR FINAL PROVIDE A CONDENSATE DRAIN TO THE MOP SINK, SCURE DIFFUSERS TO GRID, PROVIDE ACCESS TO ROOF, PROVIDE AIR BALANCE REPORT, PROGRAMS T-STAT SO FAR RUNS CONTINUOUSLY DURING OCCUPIED HOURS.
PROVIDE FIRE ALARM REPORT FOR DUCT SMOKE DETECTOR TEST.
01/13/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) INSPECTION ON DUCT WORK IN MAIN SALES AREA OK TO COVER
2) PROVIDE FRAMED OPENINGS IN CEILING FAN SUPPLY AND RETURN DIFFUSERS & VOLUMN DAMPERS IN SPIRAL PIPE