Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T10CM02205
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/12/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/08/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
03/30/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
03/25/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FINISH #1 PREVIOUS ITEM 2) SUBJECT TO BOND |
|
03/24/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WILL NEED SAFE APPROACH TO SERVICE FOR 110.26 2) GROUNDING ELECTRODE CONDUCTOR TO BE INSTALLED PER 250.30 (7) 3) BOND NEUTRAL FOR SEPERATELY ? SYSTEM 4) NEED TO PORTECT CONDUCTORS 300.4 5) TERMINATE ALL CONDUCTOR 6) NEED GUTTER ACCESS AND JUNCTION BOX 7) STILL NEED BOND POSTED 8) RECEIVED LETTER OF TORQUE |
|
03/03/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) A BOND WILL BE NEEDED FOR POWER |
|
02/24/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* |