Permit: T10CM01987

Parcel: 12112060B


Addresses:

5123 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/05/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
09/16/2011 MECHANICAL - FINAL Partial Approval 1) LETTER FROM ENGINEER OK
2) PROVIDE AN OVERFLOW SENSOR ON FAN COIL
3) NEED TO SEE THE EQUIPMENT SCHEDULE FOR FAN COIL AND CONDENSOR
4) 20 AMP FUSE MAYBE TO LARGE FOR FAN COIL
5) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX ON ROOF
6) UNITS ON ROOF OVERFUSED
7) INSTALL SUN SHIELDS OVER CANVAS CONNECTORS AT EVAP. COOLERS
8) COOLERS ARE OVERFUSED
9) A/C FAN AND EXHAUST FAN MUST RUN CONTINOUSLY DURING OCCUPIED HOURS