Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/16/2011 | MECHANICAL - FINAL | Partial Approval | 1) LETTER FROM ENGINEER OK 2) PROVIDE AN OVERFLOW SENSOR ON FAN COIL 3) NEED TO SEE THE EQUIPMENT SCHEDULE FOR FAN COIL AND CONDENSOR 4) 20 AMP FUSE MAYBE TO LARGE FOR FAN COIL 5) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX ON ROOF 6) UNITS ON ROOF OVERFUSED 7) INSTALL SUN SHIELDS OVER CANVAS CONNECTORS AT EVAP. COOLERS 8) COOLERS ARE OVERFUSED 9) A/C FAN AND EXHAUST FAN MUST RUN CONTINOUSLY DURING OCCUPIED HOURS |