Permit: T10CM01987

Parcel: 12112060B


Addresses:

5123 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
10/05/2011 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
06/20/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) DUCT NOT PROPERLY INSULATED, INSULATION IS FALLING OFF DUCT. PROVIDE STAPLES OR BANDING WIRE
2) CONDENSATE HAS BEEN INSULATED
3) G.C. HAS INFORMED ME THAT A LETTER IS FORTH COMING FROM MECH. ENGINEER TO REMOVE THE CONDENSATE CLEANOUTS FROM THE SPECS. COVER AT OWN RISK, PROVIDE LETTER PRIOR TO FINAL
06/16/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) T-STAT NOT PER ADA HEI9GHT REQUIREMENTS
2) PROVIDE ISOLATION WHERE LINE SETS PENETRATE CABINET
3) PROVIDE ACCESS DOORS FOR COND. CLEANOUTS AND O.S.A. DAMPER
4) REMOVE FROM DUCT SYSTEM ALL VOLUME DAMPERS ABOVE HARD LIDS WITHOUT ACCESS
5) PROVIDE CLEANOUTS AT ALL CONDENSATE DIRECTIONAL CHANGES
6) CONDENSATE PIPING IS TO BE INSULATED IT'S ENTIRE LENGTH