Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2011 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/20/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DUCT NOT PROPERLY INSULATED, INSULATION IS FALLING OFF DUCT. PROVIDE STAPLES OR BANDING WIRE 2) CONDENSATE HAS BEEN INSULATED 3) G.C. HAS INFORMED ME THAT A LETTER IS FORTH COMING FROM MECH. ENGINEER TO REMOVE THE CONDENSATE CLEANOUTS FROM THE SPECS. COVER AT OWN RISK, PROVIDE LETTER PRIOR TO FINAL |
|
| 06/16/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) T-STAT NOT PER ADA HEI9GHT REQUIREMENTS 2) PROVIDE ISOLATION WHERE LINE SETS PENETRATE CABINET 3) PROVIDE ACCESS DOORS FOR COND. CLEANOUTS AND O.S.A. DAMPER 4) REMOVE FROM DUCT SYSTEM ALL VOLUME DAMPERS ABOVE HARD LIDS WITHOUT ACCESS 5) PROVIDE CLEANOUTS AT ALL CONDENSATE DIRECTIONAL CHANGES 6) CONDENSATE PIPING IS TO BE INSULATED IT'S ENTIRE LENGTH |