Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/16/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CLEAN EXCESS PAINT AND FOREIGN MATERIAL FROM DEVICE TERMINALS 2) SWITCH INSTALL INCORRECTLY 3) LIGHT FIXTURES NOT PER PLANS 4) COUNTER LAYOUT NOT PER PLANS 5) WHERE ARE RECEPTS PER PLANS FOR ROLL UP DOOR AND DOOR OPERATORS 6) PLANS CALL FOR 48" HEIGHT ON SOME RECEPTS LOCATED 24" TO TOP 7) TIGHTEN LOOSE FITTINGS AT W/H 8) 4' STRIP LIGHTS NOT GROUNDED 9) BOXES MORE THAN 1/4" 314.20 10) FINISH FLOOR BOXES 11) CONTRACTORS TO BE LISTED 12) CANNOT USE SHEET METAL THREAD SCREWS FOR GROUNDING 250.8 AND CLEAN SURFACE 250.12 13) VERIFY CONDUCTOR DERATING 310.15 14) CHECK ROOF NEXT TIME 15) LABEL SERVICE DISCONNECT AND PANELS |