Permit: T10CM01889

Parcel: 11942006E

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/12/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/09/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) AIR BALANCE REPORT OK
10/25/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) ALL ROOF TOP EXHAUST FANS ARE TO BE SCREWED TO CURBS
2) MECHANICAL ROOM NOT COMPLETE
3) DUCT SMOKE DETECTOR NOT PROPERLY INSTALLED
4) PROVIDE AIR BALANCE REPORT
10/21/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) CONDENSATE NOT INSTALLED AT AIR HANDLER
2) DUCT SMOKE DETECTOR NOT PROPERLY INSTALLED AT AIR HANDLER. PLUG REMOVED FROM SAMPLE TUBE