Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HYDRONIC PIPING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/07/2011 | MECHANICAL - HYDRONIC PIPING | Approved | IVRS - Inspection :* 1) DUCT ABOVE CEILING OK TO COVER 2) HYDRO ABOVE CEILING OK TO COVER |
|
| 10/06/2011 | MECHANICAL - HYDRONIC PIPING | Not ready for Inspection | IVRS - Inspection :* | |
| 09/27/2011 | MECHANICAL - HYDRONIC PIPING | Not ready for Inspection | IVRS - Inspection :* | |
| 09/23/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* | |
| 09/22/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) HYDRO TEST ON CHILLED WATER SIDE TEST OK |
|
| 09/08/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) HYDRO MAINS TO BRANCH RUNS OK TO INSULATE |
|
| 09/06/2011 | MECHANICAL - HYDRONIC PIPING | Not ready for Inspection | IVRS - Inspection :* 1) HYDRO PRESS IS BELOW MINIMUM TEST PRESSURE REQUIREMENTS 2) OK TO INSULATE STRAIGHT RUNS, NO JOINTS, TEE'S OR BENDS |
|
| 08/22/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* | |
| 07/19/2011 | MECHANICAL - HYDRONIC PIPING | Not ready for Inspection | IVRS - Inspection :* |