Permit: T10CM01885

Parcel: 11942006E

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
07/12/2011 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
1) OK GRID LTG
07/06/2011 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) CABLES LIGHT FIXTURES TO BE SECURELY FASTENED TO BOX OR ENCLOSURE 300 NEC
2) SUPPORT LV CABLING PER MANUFACTURE RECOMMENDATION 725-800 NEC
3) EXPOSED POWER CORD NOT TO PASS THRU T-BAR OR TILE, MUST BE IN RACEWAY 400 NEC
05/23/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK HARD LIDS
05/17/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK RESTROOM HARD LIDS
2) TO AVOID REINSPECTION FEES, DO NOT CALL FOR INSPECTION UNTIL READY
3) SEE IMPORTANT NOTICE ON YELLOW PERMIT HARD
05/13/2011 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*