Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2011 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* 1) OK GRID LTG |
|
| 07/06/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) CABLES LIGHT FIXTURES TO BE SECURELY FASTENED TO BOX OR ENCLOSURE 300 NEC 2) SUPPORT LV CABLING PER MANUFACTURE RECOMMENDATION 725-800 NEC 3) EXPOSED POWER CORD NOT TO PASS THRU T-BAR OR TILE, MUST BE IN RACEWAY 400 NEC |
|
| 05/23/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK HARD LIDS |
|
| 05/17/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK RESTROOM HARD LIDS 2) TO AVOID REINSPECTION FEES, DO NOT CALL FOR INSPECTION UNTIL READY 3) SEE IMPORTANT NOTICE ON YELLOW PERMIT HARD |
|
| 05/13/2011 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |