Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10CM01741
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/01/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* EM LTGS NOT WORKING WATER HEATER, BREAKER LOCKOUTS NOT INSTALLED |
|
09/14/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK TO USE TEMP SERVICE 2) GROUNDING TO BE PER 250.8-NO SHEETMETAL THREAD 2) RECALL AFTER PROJECT COMPLETION AND REMOVAL OF EQUIPMENT |
|
07/30/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY LOUIS |
|
07/26/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) TEMP SERVICES TO BE PER TAP RULES 240 AND SERVICES 230 FOR SEPERATE STRUCTURES 2) NEED MANUFACTURES HOLDOWN FOR MAIN BREAKER 3) PROTECT CONDUCTORS AT 1 1/2" PVC 252.46 AND 300.4 4) 2ND GROUND ROD TO BE MINIMUM 6' APART |
|
07/23/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |