Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
Permit Number - T10CM01649
Inspection Description - MECHANICAL - HOODS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/07/2010 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
| 12/01/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) 2ND LAYERS OF FIRE WRAP OK 2) MECHANICAL ABOVE CEILING OK |
|
| 11/30/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) CHECKED 1ST LAYER OF FIRE WRAP OK FOR 2ND LAYER 2) 1/2" I.D. GAS FLEX NOT ADEQUATE FOR 199,999 BTU WATER HEATER 3) DO NOT REDUCE THE DRAIN SIZE FROM THE OUTLET ON MUA UNIT 4) PAINT ALL EXPOSED PLASTIC WITH LATEX PAINT 5) PROVIDE INSTALL INSTRUCTIONS FOR ACCESS DOORS 6) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX |
|
| 11/29/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) CHECKED WELDS ON GREASE DUCT-OK 1ST LAYER OF FIRE WRAP 2) ABOVE CEILING OK 3) PROVIDE INSTALL INSTRUCTIONS FOR ACCESS DOOR |
|
| 11/24/2010 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* | |
| 11/23/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) REPAIR LEAKS IN GREASE DUCT 2) PROVIDE BEADED COLLAR ON ALL CEILING DIFFUSERS |
|
| 11/22/2010 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* 1) NO MECHANICAL CONTRACTOR ON SITE TO TEST GREASE DUCT 2) BLANK OFF ALL OPENINGS 3) HAVE ACCESS TO ROOF 4) A CLEANOUT WILL BE REQUIRED ON THE HORIZONTAL SECTION OF GREASE DUCT 5) PROVIDE INSTALL INSTRUCTIONS FOR ACCESS DOORS 6) PROVIDE SMOKE TO TEST GREASE DUCT |
|
| 11/19/2010 | MECHANICAL - HOODS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO TEST GREASE DUCT PRIOR TO INSTALLING FIRE WRAP 2) NO CONTRACTOR OR SUB CONTRACTOR ON SITE 3) WHERE IS THE CLEANOUT ? |
|
| 11/01/2010 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* | |
| 10/25/2010 | MECHANICAL - HOODS | Denied | IVRS - Inspection : See detailed listing on site.| 999* |