Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T10CM01649
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/07/2010 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/01/2010 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DUCT ABOVE CEILING OK TO INSULATE 2) PROVIDE APPROVED SUPPORT FOR TYPE I HOOD 3) REMOVE TYPE I GREASE DUCT FROM INSIDE CURB TO ALOOW FOR 2 LAYERS OF FIRE WRAP |
|
| 10/25/2010 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO CONTRACTOR OR SUB CONTRACTOR ON SITE |