Permit: T10CM01592

Parcel: 133210660

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
08/29/2011 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
08/16/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SHOWER DRAIN TO LINER CONNECTION OK FOR TILE
08/15/2011 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WATER PROOFING IS APPLIED TO THE COVER HALF OF DRAIN BODY-THEN THE UPER SECTION IS BOLTED DOWN
08/10/2011 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 2 PIECE FHA DRAIN REQUIRED, WATER PROOFING SEALS TO LOWER DRAIN BODY AND WEEP HOLES REMAIN OPEN
06/06/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :* YARD PIPING OK. TESTS OK. WALLS OK TO COVER
PROVIDE FULL SIZE TOE AT WH/FUR. CORRECT VENT
RECALL FOR INSPECTION OF SHOWER PAN LINER PRIOR TO TILE. SUPPORT CLOSET FLANGE AND SECURE
06/01/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) COURTESY INSPECTION FOR NEVIN (OWNER)
2) SQUARE SHOWER DIVERTER WITH WALL AND TEST ALL JOINTS
3) SECURE YARD WATER PIPING IN WALLS
4) YARD WATER OK, PROTECT CU PENETRATING STUCCO
5) INSTALL HOSE BIB VACUUM BREAKER OR REMOVE HB
05/16/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) PLAN INDICATES 1" SUPPLY TO FIRST BRANCH
2) 1/2" SUPPLY TO (2) WASHER BOXES IS UNDERSIZED, BRING 3/4" OVER TO FIRST BRANCH
3) SECURE ALL TUBING AND PIPING AS REQUIRED
4) SECURE SHOWER VALVE SO THAT IS SQUARE WITH WALL
5) TRANSITION GLUE IS NOT APPROVED FOR USE INSIDE BLDG
6) FLANGE SHALL REST ON FINISHED FLOOR
7) CALL FOR INSPECTION SHOWER PAN LINER WHEN READY
11/05/2010 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) POINT OF VENT MAY NOT BE BELOW WEIR OF TRAP
2) PLAN INDICATES 1" CW
11/03/2010 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CLEANOUTS REQUIRED ON WASHERS AND SINKS
2) A SAN TEE MAY NOT BE USED HORIZONTALLY BELOW THE FLOOD LEVEL OF THE FIXTURE
3) A VENT MUST RISE VERTICAL TO A POINT 6" ABOVE FLOOD LEVEL
4) VENTS MAY NOT COMBINE BELOW FLOOD LEVEL
5) PROVIDE APPROVED DRAINAGE FITTINGS
6) REMOVE ANY FLUX RESIDUE FROM COPPER, ALL JOINTS IN COPPER SHALL BE REAMED
7) SECURE DIVERTER VALVE
8) PERM CAP DEMO