Permit: T10CM01592

Parcel: 133210660

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/16/2011 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*.
1) EAST AND WEST SIDES OF BLDG OK
04/11/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/05/2010 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OPEN CONDUCTORS ARE NOT APPROVED WIRING METHODS
2) SUB PANEL NOT SHOWN ON PLANS
3) BATHROOM RECEPT CIRCUIT TO SERVE NO OTHER OUTLETS
4) CEILING FANS NOT ON PLANS
5) ROMEX SHEATH TO EXTEND 1/4" MIN INTO BOX
6) ROMEX TO BE STAPLED WITHING 8" OF BOXES
7) ROMEX CANNOT BE EMBEDDED INTO CONCRETE
8) PANEL CANNOT BE INSTALLED IN CLOTHES CLOSET
9) CLOSET LIGHTS TO MEET MINIMUM CLEARANCE REQUIREMENTS NEC 410
11/03/2010 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) NEED TO CLAMP RISER TO WALL
10/07/2010 ELECTRIC - INTERMEDIATE Denied