Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/16/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :*. 1) EAST AND WEST SIDES OF BLDG OK |
|
| 04/11/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 11/05/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OPEN CONDUCTORS ARE NOT APPROVED WIRING METHODS 2) SUB PANEL NOT SHOWN ON PLANS 3) BATHROOM RECEPT CIRCUIT TO SERVE NO OTHER OUTLETS 4) CEILING FANS NOT ON PLANS 5) ROMEX SHEATH TO EXTEND 1/4" MIN INTO BOX 6) ROMEX TO BE STAPLED WITHING 8" OF BOXES 7) ROMEX CANNOT BE EMBEDDED INTO CONCRETE 8) PANEL CANNOT BE INSTALLED IN CLOTHES CLOSET 9) CLOSET LIGHTS TO MEET MINIMUM CLEARANCE REQUIREMENTS NEC 410 |
|
| 11/03/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) NEED TO CLAMP RISER TO WALL |
|
| 10/07/2010 | ELECTRIC - INTERMEDIATE | Denied |