Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/06/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LOW VOLTAGE WIRE CANNOT BE EXPOSED TO DAMAGE BY RODENTS 2) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMA FLEX 3) PROVIDE THE REQUIRED GFI SERVICE RECEPT AT THE CONDENSOR 4) PVC CANNOT BE WITHIN 6" OF THE FURNACE VENT CONNECTOR 5) PROVIDE HOSE CLAMPS AT PLASTIC HOSE CONNECTIONS 6) PROVIDE MINIMUM 3 SCREWS IN ALL JOINTS OF VENT CONNECTOR 7) DO NOT USE A 3 WAY ADAPTOR FOR FURNACE AND PUMP 8) PROVIDE THE REQUIRED SEDIMENT TRAP IN GAS LINE 9) PROVIDE AN ESCUTCHEON AROUND DBL WALL VENT AT CEILING PENETRATION 10) DO NOT TERMINATE CONDENSATE INTO A SEWER VENT. TERMINATE TO WITHIN 6" OF THE GROUND. SUPPORT COPPER LINE ON ROOF EVERY 6' |