Permit: T10CM01225

Parcel: 133032030


Addresses:

9642 E RAND PL

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/06/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LOW VOLTAGE WIRE CANNOT BE EXPOSED TO DAMAGE BY RODENTS
2) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMA FLEX
3) PROVIDE THE REQUIRED GFI SERVICE RECEPT AT THE CONDENSOR
4) PVC CANNOT BE WITHIN 6" OF THE FURNACE VENT CONNECTOR
5) PROVIDE HOSE CLAMPS AT PLASTIC HOSE CONNECTIONS
6) PROVIDE MINIMUM 3 SCREWS IN ALL JOINTS OF VENT CONNECTOR
7) DO NOT USE A 3 WAY ADAPTOR FOR FURNACE AND PUMP
8) PROVIDE THE REQUIRED SEDIMENT TRAP IN GAS LINE
9) PROVIDE AN ESCUTCHEON AROUND DBL WALL VENT AT CEILING PENETRATION
10) DO NOT TERMINATE CONDENSATE INTO A SEWER VENT. TERMINATE TO WITHIN 6" OF THE GROUND. SUPPORT COPPER LINE ON ROOF EVERY 6'