Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/25/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 06/23/2010 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) ELECTRIC NOT ON PERMIT, NOT WRITTEN UP AT LAST INSPECTION 2) NEW SUB PANEL INSTALLED 3) A GROUNDING PROBLEM EXISTS 4) THIS PAN HAS NEUTRAL AND GROUNDS THAT NEED TO BE ISOLATED ON DIFFERENT BARS 5) THE GROUND BAR THEN NEEDS TO BE BONDED TO THE METAL CABINET, THE NEUTRAL ISOLATED. THEN RUN A WIRE BACK TO SERVICE PANEL |
|
| 05/18/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* CAP OLD GAS PIPING. PROVIDE CORRECT PRESSURE RELIEF DRAING. LABEL WATER HEATER BREAKER & PUMP BREAKER |