Permit: T10CM01146

Parcel: 133040030

Inspection Status: Approved

Inspection History: SITE - SEWER

Permit Number - T10CM01146

Inspection Description - SITE - SEWER

Inspection Status - Approved

Date Description Inspector Results Comments
06/23/2015 SITE - SEWER Approved OK TO FINAL PER CHRIS KIEL
12/21/2010 SITE - SEWER Partial Approval
11/19/2010 SITE - SEWER Partial Approval IVRS - Inspection :*
1) HIGHLIGHT PER APPROVED PLAN 3 OF 3 TO BE TESTER AT LATER DATE
2) YARD WATER-PROVIDE APPROVED PLAN TEST ON RED LINE DRAWINGS
3) LOOKED AT TEST FOR DRAIN OVER (NOT APPROVED) 60' (ONLY) ON PAGE 4 OF 6 PER HIGHLIGHT 2" PVC
10/27/2010 SITE - SEWER Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SOLVENT WELD FITTINGS REQUIRE PRIMER
2) SEE UPC IS #1 SECTION 3.4.2
10/14/2010 SITE - SEWER Partial Approval IVRS - Inspection :*
1) POST AN ADDRESS
2) PIPING WITH BRANCH CONNECTIONS OK SUBJECT TO TESTING
10/08/2010 SITE - SEWER Partial Approval IVRS - Inspection :*
1) EAST 15' FROM LIFT STATION 6" THRU TO MANHOLE #1 INCLUDING (4) 6 X 4 WYES FOR HCS TO CLEANOUT #2 THRU #5
2) BEDDING, TRACER AND SHADING
3) TESTING AT LATER DATE, CONTINUATION OF HCS LATERALS LISTED AT LATER DATE