Permit: T10CM01120

Parcel: 117062200


Addresses:

135 S 4TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
11/29/2010 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
1) OK VDV CABLING
11/24/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) VERIFY LISTING, CORD AND PLUG APPLICATION FOR BOOSTER PUMP
2) FINISH STRAPING CONDUITS FOR FREEZER
3) FINISH VDV CABLING 3RD NOTICE
4) OK LIGHTS, CONDUITS, MC, AND BOXES ABOVE CEILING
5) OK ROOF, DEVICES-EXCEPT FLABOTAMY
6) PLANS CALL ALL EQUIPT TOB E LISTED AND LABELED
7) NEED TO SEE MEDICAL EQUIPMENT TO VERIFY LISTING AND CONNECTIONS
11/23/2010 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
11/15/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SEAL UNUSED CONDUIT OPENINGS
2) VDV CABLING TO BE INDEPENDENTLY SUPPORTED AND PER 725.24 AND 300.11
3) OK ELECTRIC ROOMS 100-123 EXCEPT AS NOTED